Lifting station Aqualift F Basic
Tronic, SPF 1300, 230 V
The lifting station for faecal and faecal-free wastewater is equipped with a submersible pump and a backflow preventer. The collection tank made of permanently resistant polymer (PE) offers universal connection options and has a screwed access cover. The station is controlled by a user-friendly control unit, which can be optionally integrated in the building management system via a potential-free contact or alarm and collective fault messages can be output via a GSM interface (Comfort control unit).
Item no. | 28798 |
---|---|
GTIN | 4026092074756 |
Price group | 20 |
Lifting station Aqualift F Basic Tronic, SPF 1300, 230 V
The lifting station for faecal and faecal-free wastewater is equipped with a submersible pump and a backflow preventer. The collection tank made of permanently resistant polymer (PE) offers universal connection options and has a screwed access cover. The station is controlled by a user-friendly control unit, which can be optionally integrated in the building management system via a potential-free contact or alarm and collective fault messages can be output via a GSM interface (Comfort control unit). Type of wastewater: wastewater with and without sewage Installation situation: free-standing set-up Version: Type of system: Single station Installation: Dry installation Pump control: Control unit Backflow preventer: integrated General characteristics: Colour: black Standard: EN 12050-1 Dimensions: Length: 565 mm Width: 624 mm Height: 483 mm Tank: Number of inlets: 4 ST Inlet nominal size (DN): 50 Connection for manual diaphragm pump (DN): 32 Tank volume: 50 l Pumping volume: 20 l Pressure pipe connection (DN): 80 mm Pressure pipe connection (OD): 90 mm Venting connection (DN): 70 mm Drain body: Socket version: including spigot and socket Free passage: 40 mm Pumping device: Pump: SPF 1300 Number of pumps: 1 Max. pumping capacity: 31 m3/h Max. pumping height: 8.9 m Operating voltage: 230 V Mains frequency: 50 Hz Operating mode: S3 - 15 % Power P1: 1.5 kW Power P2: 1 kW Speed: 2,650 U/min Type of fuse required (electrical protection): C 10 A Max. temperature (permanent) of conveyed material: 40 °C Weight: 24 kg Impeller type: Multi-vane impeller Length of mains cable for pump: 5 m Rated current: 6.5 A Protection class (pump): IP 68 (3m/48h) Protection class: I Insulation class: F Control: Control unit: Basic Operating voltage: 230 V Mains frequency: 50 Hz Self-diagnosis system (SDS): no Battery buffering: yes Multi-line display: no Log book function: no Potential-free contact: optional Motor protection switch: yes Protection class control unit: IP 54 Length of mains cable for control unit: 5 m Type of level measurement: mechanical Alarm sensor: Float switch
Installation Video
Title | Item no. |
---|
Title | Item no. |
---|
Title | Item no. | ||
---|---|---|---|
Elastic union joint for hoses Ø 110 | 28663 | Show | |
Flange joint DN 100, for polymer fittings | 28712 | Show | |
Shut-off valve DN 80, Polymer, vert | 28715 | Show | |
Shut-off valve DN 80, Polymer, vertical with flange | 28716 | Show | |
Hole saw for DN 50/70/100 | 500101 | Show | |
Seal for pipe penetration, DN 50 | 850114 | Show | |
Seal for channel passage 75 mm | 850116 | Show | |
Seal for channel passage 110 mm | 850117 | Show |
Title | Item no. |
---|
Catalog Page | |
---|---|
Manuals | |
CAD Data | |
Test Reports and Certificates | |
Declaration of Performance |
- Declaration of Performance (DOP) (ATTR-292): 009-038
- Net weight (ATTR-A3A): 22 KGM
- Gross weight (ATTR-A3B): 24.3 KGM
- - (ATTR-370):
- Area of application (ATTR-264): drainage
- Pump type (ATTR-265): Freestanding pump
- Pump shaft position (ATTR-266): vertical
- Pump design (ATTR-267): Dry rotor pump
- Pump hydraulics (ATTR-268): single stage
- Pump suction characteristic (ATTR-269): non-self-priming
- Pump drive (ATTR-270): E-motor for alternating current
- E-motor, type of startup (ATTR-271): direct
- Pump casing material (ATTR-272): Polymer
- Upper tolerance of the operating voltage (+) (ATTR-273): 10 PROZ
- Lower tolerance of the operating voltage (-) (ATTR-274): 10 PROZ
- Upper tolerance of the nominal frequency (+) (ATTR-275): 3 PROZ
- Lower tolerance of the nominal frequency (-) (ATTR-276): 2 PROZ
- Pump electrical connection (ATTR-277): 1/N/PE 230V
- Startup circuit for three-phase connection or three-phase current (ATTR-278):
- Motor pump shaft (ATTR-279): continuous
- Shaft seal (ATTR-280): RSSR
- Minimum pumped media temperature (ATTR-282): 0 CEL
- Maximum operating pressure (Pmax) (ATTR-283): 890 HPA
- Start-up current (ATTR-285): 14.9 AMP
- Pump (ATTR-4): SPF 1300
- Number of pumps (ATTR-181): 1
- Impeller type (ATTR-8): Multi-vane impeller
- Type of fuse required (electrical protection) (ATTR-N3): C 10 A
- Operating mode (ATTR-10): S3 - 15 %
- Power P1 (ATTR-F4): 1.5 KWT
- Power P2 (ATTR-F5): 1 KWT
- Speed (ATTR-F2): 2,650 UMIN
- Operating voltage (ATTR-131): 230 VLT
- Mains frequency (ATTR-N4): 50 HTZ
- Rated current (ATTR-N5): 6.5 AMP
- Max. pumping capacity (ATTR-F7): 31 MQH
- Max. pumping height (ATTR-F8): 8.9 MTR
- Max. temperature (permanent) of conveyed material (ATTR-132): 40 CEL
- Protection class (ATTR-133): I
- Protection class (pump) (ATTR-125): IP 68 (3m/48h)
- Length of mains cable for pump (ATTR-11): 5 MTR
- Weight (ATTR-191): 24 KGM
- Insulation class (ATTR-193): F
- Number of inlets (ATTR-B1B): 4 PCE
- Inlet nominal size (DN) (ATTR-B1CA): 50 MMT
- Venting connection (DN) (ATTR-B4): 70 MMT
- Connection for manual diaphragm pump (DN) (ATTR-B4B): 32
- Pressure pipe connection (DN) (ATTR-B17): 80 MMT
- Pressure pipe connection (OD) (ATTR-B18): 90 MMT
- Tank volume (ATTR-B9): 50 LTR
- Pumping volume (ATTR-B10): 20 LTR
- Length (ATTR-A6A): 565 MMT
- Width (ATTR-A6B): 624 MMT
- Height (ATTR-A6C): 483 MMT
- Volume (ATTR-320): 0.2 MTQ
- Packaging dimension: length (ATTR-325): 610 MMT
- Packaging dimension: width (ATTR-326): 610 MMT
- Packaging dimension: height (ATTR-327): 490 MMT
- Dimensions (ATTR-323): 610X610X490MM
- Number of packages (ATTR-321): 0
- Type of system (ATTR-2): Single station
- Installation (ATTR-164): Dry installation
- Backflow preventer (ATTR-165): integrated
- Pump control (ATTR-134): Control unit
- Socket version (ATTR-233): including spigot and socket
- Control unit (ATTR-S2): Basic
- Self-diagnosis system (SDS) (ATTR-S5): no
- Battery buffering (ATTR-S6): yes
- Multi-line display (ATTR-S7): no
- Log book function (ATTR-S8): no
- Potential-free contact (ATTR-S11): optional
- Length of mains cable for control unit (ATTR-S12): 5 MTR
- Operating voltage (ATTR-S13): 230 VLT
- Mains frequency (ATTR-S14): 50 HTZ
- Protection class control unit (ATTR-S4): IP 54
- Alarm sensor (ATTR-S1): Float switch
- Type of level measurement (ATTR-7A): mechanical
- Motor protection switch (ATTR-172): yes
- - (ATTR-S21):
- - (ATTR-S22):
- - (ATTR-S23):
- Standard (ATTR-9): EN 12050-1
- CE marking (ATTR-A5B): yes
- Installation situation (ATTR-1): free-standing set-up
- Free passage (ATTR-180): 40 MMT
- Type of wastewater (ATTR-6): wastewater with and without sewage
- Colour (ATTR-102): black
- External monitoring (ATTR-A8): LGA
- TÜV test mark (ATTR-376): ID 1111241940